FX2N-8EYT

FX2N-8EYT

Output extension block FX 2 N – 8 EYT

$55.44

  • Estimated Lead Time : In stock. Usually ships in 7-10 working days.
  • Manufacturer : Mitsubishi Electric
  • FX2N-8EYT
  • Output extension block FX 2 N – 8 EYT
  • Application sequencer : FX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UCFX2NC – CNV – IF is required for connection to FX1NC and FX2NC. To connect to FX3GC, FX3UC, FX2NC – CNV – IF or FX3UC – 1PS – 5V is required.
  • mass : 0.2 Kg
  • Rated voltage : Internal power supply from the sequencer
  • Number of output points : 8 points
  • Output connection shape : Vertical terminal block (M3 screw)
  • Output type / format : Transistor / sink output
  • External power supply : DC 5V to 30V
  • Maximum load Resistive load : The total load current per 0.5 A / point common should be as follows. . Output 4 points / common: 0.8 A or less . Output 8 points / common: 1.6 A or less
  • Inductive load : 12 W / DC 24 V
  • Open-circuit leakage current : 0.1 mA / DC 30 V
  • ON voltage : 1.5V or less
  • Response time OFF ??ON : 0.2 ms or less / 200 mA (24 VDC)
  • ON ??OFF : 0.2 ms or less / 200 mA (24 VDC)
  • Circuit insulation : Photocoupler insulation
  • Output operation indication : LED on the panel when driving the photo coupler
  • Ambient temperature : 0 to 55 掳 C. … Operating -25 to 75 掳 C. ….. Save
  • Relative humidity : 5 to 95% RH (noncondensing)…. in operation
  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (80 minutes in total in total) The criterion is based on IEC 61131-2
  • Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
  • Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
  • Impact resistance : 147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
  • Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 渭s, rising 1 ns, with noise si
  • tor with period of 30 to 100 Hz
  • Withstand voltage : Between the output terminal (transistor) of the expansion output block and the earth terminal: AC 500 V for 1 minute
  • Insulation resistance : Between the output terminal (transistor) and the earth terminal of the expansion output block: 5 M惟 or more with DC 500 V insulation resistance meter
  • Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
  • Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
  • Shipping Weight : 1.2 Kg