| Type | Range | Resolution |
|---|---|---|
| RTD (Pt) | Pt 100, Pt 200, Pt 500, Pt 1000 | 16-bit incl. sign |
| RTD (Ni) | Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000 | 16-bit incl. sign |
| RTD (Cu) | Cu 10 | 16-bit incl. sign |
| Resistance | 150 Ω, 300 Ω, 600 Ω, 3 kΩ, 6 kΩ | 15-bit |
| Thermocouple | E, N, J, K, L, S, R, B, T, C, U, TXK | 16-bit incl. sign |
| Voltage | ±50 mV, ±80 mV, ±250 mV, ±1 V | 16-bit incl. sign |
The module supports 2-wire, 3-wire, and 4-wire connection for resistance and RTD measurement .
The 6ES7134-6JD00-0CA1 weighs approximately 32 g (net weight) . Some distributor listings show a gross weight of 39–40 g including packaging .
The official Siemens manual for this module covers:
Product overview and properties
Wiring and block diagram
Parameters and address space
Analog value representation
Diagnostics
The manual is available in multiple languages, including English, German (Handbuch), Italian (manuale), Spanish, and French .
The module uses 2-wire, 3-wire, or 4-wire connection depending on the measurement type:
RTD 4-wire: Highest accuracy. Constant current is supplied through I+ and I- terminals, voltage is measured across M+ and M-.
RTD 3-wire: Automatic cable resistance compensation. Very accurate measurement .
RTD 2-wire: Lower accuracy due to line resistance. Use only for short cable runs.
Thermocouple (TC): Requires BaseUnit type A1 for internal cold junction compensation .
Voltage measurement: Connect signal to M+ and M- terminals.
Supported BaseUnits: BU type A0 and A1 .
Color code: CC00 .
Supply voltage monitoring (PWR-LED)
Channel status display (green LED)
Module diagnostics (green/red LED)
Wire-break detection
Overflow/underflow detection
Reference junction diagnostics (for TC measurement)
Channel-based programmable diagnostics
| Component | Order Number |
|---|---|
| BaseUnit Type A0 | 6ES7193-6BP00-0DA0 |
| BaseUnit Type A0 (continuation) | 6ES7193-6BP00-0BA0 |
| BaseUnit Type A1 | 6ES7193-6BP10-0BA0 |
| BusAdapter BA 2xRJ45 | 6ES7193-6AR00-0AA0 |
| Interface Module IM 155-6 PN | 6ES7155-6AU01-0CN0 |
Temperature measurement (RTD and TC)
Machine manufacturing
Process automation
Packaging lines
Factory automation
Distributed I/O systems
Q: What is the difference between 6ES7134-6JD00-0CA1 and 6ES7134-6HD01-0BA1?
A: 6JD00-0CA1 is a high-feature temperature module for RTD, TC, resistance, and voltage. 6HD01-0BA1 is a standard analog input module for voltage and current (2-wire). Choose based on your sensor type.
Q: What is the weight of 6ES7134-6JD00-0CA1?
A: Approximately 32 g (net weight) .
Q: What BaseUnit do I need for this module?
A: Use BU type A0 or A1. For thermocouple measurement with internal cold junction compensation, BaseUnit type A1 is required .
Q: Does this module support 2-wire, 3-wire, and 4-wire connection?
A: Yes. It supports all three connection methods for RTD and resistance measurement .
Q: What is the difference between 6ES7134-6JD00-0CA1 and 6ES7134-6JD00-2CA1?
A: They are the same module. The -2CA1 version is a 10-piece packaging unit, while -0CA1 is a single unit.
Q: Where can I find the manual (Handbuch/manuale)?
A: The official manual is available from Siemens Industry Online Support. Contact us if you need a copy.
We supply 6ES7134-6JD00-0CA1, BaseUnits, BusAdapters, and related ET 200SP components.
Send us your quantity and destination, and we will quote you our best price.