CC-Link small type remote I / O unit (transistor output, terminal block)
AJ65SBTB1 – 16T
Output format : Transistor output (sink type)
Number of output points : 16 points
Rated load voltage : DC12 / 24V
Used load voltage range : DC 10.2 to 26.4 V (ripple ratio within 5%)
Maximum load current : 0.5 A / 1 point, 3.6 A / 1 common
Maximum inrush current : 1.0 A less than 10 ms
Leakage current at OFF : 0.25 mA or less
Maximum voltage drop during ON : DC 0.3 V or less (TYP.) 0.5 A, DC 0.6 V or less (MAX.) 0.5 A
Output response time OFF ??ON : 0.5ms or less
ON ??OFF : 1.5 ms or less (resistance load)
Surge suppressor : Zener diode
Protection function : Overload protection function, overvoltage protection function, overheat protection function
Output section External power supply Voltage : DC 10.2 to 26.4 V (ripple ratio within 5%)
Current : 30 mA or less (TYP. DC 24 V, per common) External load current is not included
Output common method : 16 points 1 common (terminal trapezoid 1 wire type)
Output isolation method : Photocoupler isolation
Withstand voltage : Between DC external terminal and ground: AC 500 V for 1 minute
Insulation resistance : DC external terminal collective to ground: 500 VDC DC insulation resistance meter 10 M惟 or more
Protection grade : IP2X
Station type : Remote I / O station
Number of occupied stations : 1 station
Unit power supply Voltage : DC 20.4 to 26.4 V (ripple ratio within 5%)
Current : 50 mA or less (24 VDC, all points ON)
External wiring connection method : Communication unit, Unit power supply unit: 7 points 2-piece terminal block (M3 screw) I / O power supply unit, input / output unit: 18 points Direct mounting terminal block (M3 screw)
External dimensions Height (H) : 50 mm
Width (W) : 118 mm
Depth (D) : 40 mm
mass : 0.18 Kg
Operating ambient temperature : 0 to 55 掳 C
Storage ambient temperature : -20 to 75 掳 C
Ambient operating humidity : 10 to 90% RH, non condensing
Storage ambient humidity : 10 to 90% RH, non condensing
Anti-vibration Meets JIS B 3502, IEC 61131-2 When there is intermittent vibration : Frequency: 5 to 8.4 Hz, One amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m / s 2 Sweep count: 10 times in X, Y, Z directions
When there is continuous vibration : Frequency: 5 to 8.4 Hz, One amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m / s 2
Impact resistance : Meets JIS B 3502, IEC 61131-2 (147 m / s 2 , 3 times in each of X, Y and Z directions)
Use atmosphere : No corrosive gas
Use elevation : 0 to 2000 m
Installation location : In the control panel
Over voltage category : II or less
Pollution degree : 2 or less
Shipping Weight : 1.2 Kg