Estimated Lead Time : In stock. Usually ships in 7-10 working days.
Manufacturer : Mitsubishi Electric
FX2N-16EYR
Output expansion block FX2N – 16EYR
Application sequencer FX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UC
<Connecting to connector type sequencer>
FX2NC – CNV – IF is required for connection to FX1NC and FX2NC.
To connect to FX3GC, FX3UC, FX2NC – CNV – IF or FX3UC – 1PS – 5V is required.
mass 0.3 kg
Power supply specification
Rated voltage Internal power supply from the sequencer
Output specification
Number of output points 16 points
Output connection shape Vertical terminal block (M3 screw)
Output type / format relay
External power supply AC 250 V DC 30 V or less
Maximum load Resistive load
Total load current of 2A / 1 point common per resistance load should be as follows.
Output 4 points / common: 8 A or less
Output 8 points / common: 8 A or less
Maximum load Inductive load 80VA
Minimum load DC 5 V 2 mA (reference value)
Response time (OFF ? ON) About 10 ms
Response time (ON ? OFF) About 10 ms
Circuit insulation Mechanical insulation
Output operation indication When the relay coil is energized LED on the panel is lit
Ambient temperature 0 to 55 掳 C. Operating -25 to 75 掳 C. Save
Relative humidity 5 to 95% RH (noncondensing) in operation
Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The
criteria are based on IEC 61131-2
Anti-vibration When DIN rail is installed Frequency: 57 to 150 Hz Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (total of 80 minutes each) The
criterion is based on IEC 61131-2
Anti-vibration Direct installation Frequency: 10 to 57 Hz One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The
criteria are based on IEC 61131-2
Anti-vibration Direct installation Frequency: 57 to 150 Hz Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The
criteria are based on IEC 61131-2
Impact resistance 147 m / s 2 , working time 11 ms,
criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
Noise immunity Noise voltage with 1,000 Vp-p, noise width 1 碌s, rising 1 ns, with noise si
tor with period of 30 to 100 Hz
Withstand voltage Between the output terminal (relay) and the earth terminal of the expansion output block: AC 1500 V for 1 minute
Insulation resistance Between the output terminal (relay) and the earth terminal of the expansion output block: 5 MO or more with DC 500 V insulation resistance meter
Use atmosphere There is no corrosive property, flammable gas, conductive dust (dust) is not serious
Use altitude
Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
Shipping Weight : 1.3 Kg