FX2N-32CCL

FX2N-32CCL

CC-Link system interface block (remote device station) FX2N-32CCL

$152.46

  • Estimated Lead Time : In stock. Usually ships in 7-10 working days.
  • Manufacturer : Mitsubishi Electric
  • FX2N-32CCL
  • CC-Link system interface block (remote device station)
  • FX2N-32CCL
  • CC-Link version : Ver.1.00
  • Station type : Remote device station
  • Insulation method : The network bus and the internal power supply are photocoupler isolated
  • Transmission speed : 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps selectable (set with rotary switch)
  • Station number : 1 to 64 stations (set with rotary switch)
  • Number of occupied stations : 1 to 4 stations (set with rotary switch)
  • Maximum cable total extension (maximum transmission distance) : Different according to transmission speed up to 1200 m
  • Number of remote I / O points : The number of remote I / O points per station is 32 input points and 32 output points. However, the upper 16 points of the last station are occupied by the CC-Link system as the system area.
  • Remote register point number : The number of remote registers per station is 4 RW write areas, 4 RW read areas.
  • Number of links per station : Remote input / output 32 points / 32 points (RX / RY) However, the upper 16 points of the last station are occupied by the CC-Link system as a system area. Remote register (RWw) 4 points (Master station ??Remote device station) Remote register (RWr) 4 points (Remote device station ??Master station)
  • Communication method : Polling method
  • Synchronization method : Frame synchronization method
  • Coding scheme : NRZI system
  • Transmission path format : Bus (RS-485)
  • Transmission format : HDLC compliant
  • Error control method : CRC (X 16 + X 12 + X 5 + 1)
  • Connection cable : CC-Link dedicated cable, CC-Link exclusive high-performance cable CC-Link exclusive cable and CC-Link exclusive high-performance cable can not be mixed.
  • Communicate with the sequencer : Performing via buffer memory with FROM / TO instruction
  • Display (LED) : RD, SD, L RUN, L ERR, POWER
  • Number of occupied I / O points : 8 points (It can count either input or output)
  • Application sequencer : FX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UCFX2NC – CNV – IF is required for connection to FX1NC and FX2NC. To connect to FX3GC, FX3UC, FX2NC – CNV – IF or FX3UC – 1PS – 5V is required.
  • mass : 0.2 Kg
  • Power supply : DC 5 V internal power supply: Power is supplied from the sequencer via extension cable. DC 24 V external power supply (24 VDC 卤 10%): Power is supplied from the external terminal block.
  • Current consumption : DC 5 V internal power supply: 130 mA DC 24 V external power supply: 50 mA
  • Ambient temperature : 0 to 55 掳 C. … Operating -25 to 75 掳 C. ….. Save
  • Relative humidity : 5 to 95% RH (noncondensing)…. in operation
  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
  • Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
  • Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
  • Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
  • Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 渭s, rising 1 ns, with noise si
  • tor with period of 30 to 100 Hz
  • Withstand voltage : Between external terminals and ground terminal: 500 VAC for 1 minute
  • Insulation resistance : Between external terminal and ground terminal: 500 MV DC 500 M惟 or more with insulation resistance meter
  • ground : Class D grounding (grounding resistance: 100 惟 or less)Grounding should be dedicated ground or common ground.
  • Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
  • Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
  • Shipping Weight : 1.2 Kg