  • Manufacturer : Mitsubishi Electric
  • Application sequencer : FX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UC FX2NC – CNV – IF is required for connection to FX1NC and FX2NC. To connect to FX3GC, FX3UC, FX2NC – CNV – IF or FX3UC – 1PS – 5V is required.
  • mass : 0.2 kg
  • Rated voltage : Internal power supply from the sequencer
  • Number of input points : 8 points
  • Input connection shape : Vertical terminal block (M3 screw)
  • Input format : sink
  • Input signal voltage : DC 24 V + 10%
  • Input impedance : 4.3 kO
  • Input signal current : 5 mA / 24 VDC
  • Input ON sensitivity current : 3.5 mA or more
  • Input OFF sensitivity current : 1.5 mA or less
  • Input response time : About 10 ms
  • Input signal format : No-voltage contact input NPN or open collector transistor
  • Input circuit insulation : Photocoupler insulation
  • Input operation display : LED on the panel when input is ON
  • Ambient temperature Relative humidity Impact resistance Noise immunity Withstand voltage Insulation resistance Use atmosphere Use altitude : 0 to 55 o C. &bull&bull&bull Operating -25 to 75 o C. &bull&bull&bull&bull&bull Save, 5 to 95% RH (noncondensing)&bull&bull&bull&bull in operation
  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (total of 80 minutes each) The criterion is based on IEC 61131-2
  • Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
  • Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
  • 147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
  • Noise voltage with 1,000 Vp-p, noise width 1 us, rising 1 ns, with noise simulator with period of 30 to 100 Hz
  • Between the input terminal of the expansion input block and the ground terminal: 500 V AC for 1 minute
  • Between the input terminal of the expansion input block and the earth terminal: 500 VDC or more 5 MO or more with the insulation resistance meter
  • There is no corrosive property, flammable gas, conductive dust (dust) is not serious
  • Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
  • Shipping Weight: 2 kg