FX2NC-16EX

FX2NC-16EX

FX2NC-16EX — Mitsubishi — Input extension block

$94.50

  • Estimated Lead Time : In stock. Usually ships in 3 – 5 working days.
  • Manufacturer : Mitsubishi Electric
  • FX2NC-16EX
  • Input extension block
  • Application sequencer : FX1NC, FX3GC, FX2NC, FX3UC
  • mass : 0.15 Kg
  • Rated voltage : Internal power supply from the sequencer
  • power consumption : 2.2 W
  • Input specification :
  • Number of input points : 16 points
  • Input connection shape : connector
  • Input format : sink
  • Input signal voltage : DC 24 V + 20% – 15% ripple (pp) within 5%
  • Input impedance : 4.3 kO
  • Input signal current : 5 mA / 24 VDC
  • Input ON sensitivity current : 3.5 mA or more
  • Input OFF sensitivity current : 1.5 mA or less
  • Input response time : About 10 ms
  • Input signal format : No-voltage contact input or NPN open collector transistor
  • Input circuit insulation : Photocoupler insulation
  • Input operation display : LED ON when input is ON
  • Ambient temperature : 0 to 55 掳 C. … Operating -20 to 70 掳 C. … Save
  • Relative humidity : 35 to 85% RH (noncondensing)…. in operation
  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (80 minutes in total in total) The criterion is based on IEC 61131-2
  • Impact resistance : 147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
  • Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 碌s, rising 1 ns, with noise si
  • tor with period of 30 to 100 Hz
  • Withstand voltage : Between the input terminal of the expansion input block and the ground terminal: 500 V AC for 1 minute
  • Insulation resistance : Between the input terminal of the expansion input block and the earth terminal: 500 VDC or more 5 MO or more with the insulation resistance meter
  • Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
  • Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
  • Shipping Weight : 1.2 Kg