Estimated Lead Time : In stock. Usually ships in 7-10 working days.
Manufacturer : Mitsubishi Electric
FX3U-3A-ADP
Analog input / output adapter FX3U – 3A – ADP
Analog input Analog input range Voltage input : DC 0 to 10 V (input resistance 198.7 k惟)
Current input : DC 4 to 20 mA (input resistance 250 惟)
Number of input channels : 2 channels
Absolute maximum input Voltage input : -0.5 V, +15 V
Current input : -2 mA, +30 mA
Input characteristics : Input mode (voltage / current input) can be set for each channel.
Digital output : 12 bit binary
resolution Voltage input : 2.5 mV (10 V x 1/4000)
Current input : 5 渭A (16 mA X 1/3200)
Overall precision Voltage input : Ambient temperature 25 掳 C 卤 5 掳 C 卤 0.5% (卤 50 mV) to full scale 10 V Ambient temperature 0 掳 C to 55 掳 C 卤 1.0% (卤 100 mV) to full scale 10 V
Current input : Ambient temperature 25 掳 C 卤 5 掳 C 卤 0.5 % (卤 80 渭A) against full scale 16 mA Ambient temperature 0 掳 C to 55 掳 C 卤 1.0% (卤 160 渭A) for full scale 16 mA
A / D conversion time When FX3U / FX3UC sequencer is connected : 80 渭s X Number of used input channels + 40 渭s X Number of output output channels (data update every calculation cycle)
When FX3S / FX3G / FX3GC programmable controller is connected : 90 渭s X number of used input channels + 50 渭s X number of output output channels (data update every calculation cycle)
Insulation method : . Insulation between analog input / output section and sequencer by photo coupler . Insulation between drive power supply and analog input / output section by DC / DC converter . No isolation between each channel
Analog output Analog output range Voltage output : DC 0 to 10 V (external load resistance 5 k to 1 M惟)
Current output : DC 4 to 20 mA (external load resistance 500 惟 or less)
Number of output channels : 1 channel
Output characteristics : Output mode (voltage / current output) can be set.
Digital input : 12 bit binary
resolution Voltage output : 2.5 mV (10 V x 1/4000)
Current output : 4 渭A (16 mA X 1/4000)
Overall precision Voltage output : Ambient temperature 25 掳 C 卤 5 掳 C 卤 0.5% (卤 50 mV) to full scale 10 V Ambient temperature 0 掳 C to 55 掳 C 卤 1.0% (卤 100 mV) to full scale 10 V External load resistance (Rs) is less than 5 k惟 In addition, the following calculations increase. (It increases by 100 mV per 1%.) 47 X 100 / (Rs + 47) – 0.9 (%)
Current output : Ambient temperature 25 掳 C 卤 5 掳 C 卤 0.5 % (卤 80 渭A) against full scale 16 mA Ambient temperature 0 掳 C to 55 掳 C 卤 1.0% (卤 160 渭A) for full scale 16 mA
D / A conversion time When FX3U / FX3UC sequencer is connected : 80 渭s X Number of used input channels + 40 渭s X Number of output output channels (data update every calculation cycle)
When FX3S / FX3G / FX3GC programmable controller is connected : 90 渭s X number of used input channels + 50 渭s X number of output output channels (data update every calculation cycle)
Insulation method : . Insulation between analog input / output section and sequencer by photo coupler . Insulation between drive power supply and analog input / output section by DC / DC converter . No isolation between each channel
Number of occupied I / O points : 0 point (It does not relate to the maximum input / output point number of the sequencer)
Application sequencer : FX3S, FX3G (Ver.1.20 or later), FX3U (Ver.2.61 or later), FX3GC, FX3UC (Ver.2.61 or later) FX3S – CNV – ADP is required for connection to FX3S. For connection to FX 3 G, FX 3 G – CNV – ADP is required. To connect to FX3U and FX3UC – 32MT – LT (-2), a function expansion board is required.
mass : About 0.1 Kg
Power supply Conversion circuit drive power supply : DC24 V + 20% -15% 90 mA Connect a 24 VDC power supply to the terminal block and supply it.
Interface drive power supply : DC 5 V 20 mA Internal power is supplied from the DC 5 V power supply of the basic unit.
Ambient temperature : 0 to 55 掳 C. … Operating -25 to 75 掳 C. ….. Save
Relative humidity : 5 to 95% RH (noncondensing)…. in operation
Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 渭s, rising 1 ns, with noise si
tor with period of 30 to 100 Hz
Withstand voltage : Between all terminals and ground terminal: 500 VAC for 1 minute
Insulation resistance : Between all terminals and ground terminal: 500 MV DC 500 M惟 or more with an insulation resistance meter
ground : Class D grounding (grounding resistance: 100 惟 or less)Grounding should be dedicated ground or common ground.
Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
Shipping Weight : 1.1 Kg