Manufacturer : Mitsubishi Electric
FX3U-4AD-TC-ADP
Analog input adapter for thermocouple type temperature sensor FX3U – 4AD – TC – ADP
Temperature sensor . temperature control input signal : Thermocouple K type or J type JIS C 1602-1995 However, please use the same type thermocouple of all channels.
Number of input channels : 4 channels
Rated temperature range K type : -100 掳 C to + 1000 掳 C (-148 掳 F to + 1832 掳 F)
J type : -100 掳 C. to + 600 掳 C. (-148 掳 F. to + 1112 掳 F.)
Digital output K type : -1000 to +10000 (-1480 to + 18320 ) Within parentheses, the digital value at Fahrenheit setting
J type : -1000 to +6000 (-1480 to + 11120 ) Within (), the digital value at Fahrenheit setting
resolution K type : 0.4 掳 C (0.72 掳 F)
J type : 0.3 掳 C (0.54 掳 F)
Overall accuracy : 卤 0.5% of full scale + 1 掳 C
control method : Depending on the sequence program
Conversion speed FX3U / FX3UC PLC : 200 渭s (Data update every calculation cycle)
FX3S / FX3G / FX3GC Sequencer : 250 渭s (Data update every calculation cycle)
Insulation method : . Isolation between analog input part and sequencer by photo coupler . Insulation between analog input part and power supply by DC / DC converter . No isolation between each channel
Number of occupied I / O points : 0 point (It does not relate to the maximum input / output point number of the sequencer)
Application sequencer : FX3S, FX3G, FX3U, FX3GC, FX3UC (FX3UC – 32MT – LT is Ver.1.30 or later) FX3S – CNV – ADP is required for connection to FX3S. For connection to FX 3 G, FX 3 G – CNV – ADP is required. To connect to FX3U and FX3UC – 32MT – LT (-2), a function expansion board is required.
mass : 0.1 Kg
Power supply specification
Power supply : DC 5 V 15 mA (internal power supply from the sequencer) DC 24 V + 20% -15% 45 mA (external power supply)
Ambient temperature : 0 to 55 掳 C. … Operating -25 to 75 掳 C. ….. Save
Relative humidity : 5 to 95% RH (noncondensing)…. in operation
Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 渭s, rising 1 ns, with noise si
tor with period of 30 to 100 Hz
Withstand voltage : Between all terminals and ground terminal: 500 VAC for 1 minute
Insulation resistance : Between all terminals and ground terminal: 500 MV DC 500 M惟 or more with an insulation resistance meter
ground : Class D grounding (grounding resistance: 100 惟 or less) Grounding should be dedicated ground or common ground.
Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
Shipping Weight : 1.1 Kg