Estimated Lead Time : 7-10 working days.
Manufacturer : Mitsubishi Electric
Product No : FX3U-4HSX-ADP
Product type : High Speed Input Adapter
Number of input channels : 4 ch
Input format : Differential line receiver (equivalent to AM 26 C 32)
Input voltage : DC 5V
Maximum response frequency 1 phase 1 input : 200 kHz (by sequence program)
1 phase 2 input : 200 kHz (by sequence program)
2 phase 2 input : 100 kHz It is a high-speed counter operating with a hardware counter (by sequence program) . The maximum input frequency of the software counter is the same as when it is loaded to the input terminal of the basic unit. It also includes cases where the hardware counter operates as a software counter.
Count range : -2, 147, 483, 648 – + 2, 147, 483, 647
Count mode : Depending on the sequence program
Matching output (comparison) : Depending on the sequence program
Insulation method : Insulation between external wiring of the input part and the sequencer by photocouplers and transformers
Display (LED) : X 0/3, X 1/4, X 2/5, X 6/7, POWER
Number of occupied I / O points : When connecting the first unit: Use X000 ~ X002, X006 When connecting the second unit: Use X003 ~ X005, X007
Application sequencer : A function expansion board is required when connecting the FX3U analog / communication adapter. It is unnecessary when only high-speed input / output adapter is connected.
mass : 0.08 Kg
Power supply : DC 5 V 30 mA (internal power supply from PLC) DC 24 V 30 mA (internal power supply from PLC)
Ambient temperature : 0 to 55 掳 C. … Operating -25 to 75 掳 C. ….. Save
Relative humidity : 5 to 95% RH (noncondensing)…. in operation
Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 碌s, rising 1 ns, with noise si
tor with period of 30 to 100 Hz
Withstand voltage : High-speed input Between the input terminal of the special adapter and the earth terminal of the PLC main unit: AC 500 V for 1 minute
Insulation resistance : High speed input Between the input terminal of the special adapter and the earth terminal of the programmable controller main body: DC 500 V Insulation resistance meter 5 MO or more
ground : Class D grounding (grounding resistance: 100 O or less)Grounding should be dedicated ground or common ground.
Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
Weight : 0.08kg
Shipping Weight : 1 Kg