Estimated Lead Time : In stock. Usually ships in 7-10 working days
Manufacturer : Honeywell
Application : On-Off Primary Control with Prepurge
Dimensions (in.) : 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
Dimensions (mm) : 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase
Used With : 7800 Series Amplifiers
Weight (lb) : 1 lb 15 oz
Weight (kg) : 0.9 kg
Frequency : 50 Hz; 60 Hz (卤10%)
Approvals, Underwriters Laboratories Inc. : Component Recognized, File No. MP268; Guide No. MCCZ.
Approvals, Canadian Standards Association : Certified, File No. LR95329-3.
Voltage : 120 Vac (+10, -15%)
Shipping and Storage Temperature Range (F) : -40 F to +140 F
Shipping and Storage Temperature Range (C) : -40 C to +60 C
Approvals, Federal Communications Commission : FCC Part 15, Class B, Emissions.
Flame Establishing Period – Pilot : 4 sec or 10 sec
Flame Establishing Period -Main : Intermittent
Interlocks : Selectable
PrePurge : Determined by ST7800A Purge Timer Card
Required Components : Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Delayed Main Valve : No
Pilot Type : intermittent
Vibration : 0.5 G environment
Approvals, Control Safety Devices : Acceptable: CSD-1
Approvals, Swiss RE : Acceptable
Approvals, Factory Mutual : Report No. OX4A5.AF.
Shipping Weight : 2.9 Kg