Estimated Lead Time : In stock. Usually ships in 7-10 working days
Manufacturer : Mitsubishi Electric
Temperature adjustment block FX2N-2LC
Temperature sensor, temperature controlNumber of input points2 points
Type of inputthermocoupleK, J, R, S, E, T, B, N, PLII, WRe 5-26, U, L JIS C 1602-1995
Resistance temperature detector3-wire type Pt100 JIS C 1604-1997 (new JIS) JPt 100 JIS C 1604-1981 (old JIS)
Measurement accuracyAmbient temperature 23 掳 C 卤 5 掳 C: Input range 卤 0.3% 卤 1 digit Ambient temperature 0 掳 C to 55 掳 C: Input range 卤 0.7% 卤 1 digit However, B input 0 to 399 掳 C (0 to 799 掳 F) and PLII , 0 to 32 掳 F of WRe5-26 input is out of guaranteed accuracy range
Cold junction temperature compensation errorWithin 卤 1.0 掳 C. However, the input value is within 卤 2.0 掳 C at -150 to -100 掳 C, and 卤 3.0 掳 C at -200 to -150 掳 C.
resolution0.1 掳 C (0.1 掳 F) or 1 掳 C (1 掳 F) Depends on the input range of the sensor used.
Sampling period500 ms
Influence of external resistanceAbout 0.35 渭V / 惟
Input impedance1 M惟 or more
Sensor currentAbout 0.3 mA
Permissible input wire resistance10 惟 or less
Operation at input break / short circuitUpscale / downscale
Current detector (CT) input (number of inputs)2 points
Current detector (CT) input (current detector)CTL-12-S36-8 or CTL-6-PH (made by usd)
Current detector (CT) input (heater current measurement value)When using CTL-12: 0.0 to 100.0 A When using CTL-6: 0.0 to 30.0 A
Current detector (CT) input (measurement accuracy)卤 5% of the input value or 2A, whichever is larger (excluding the accuracy of the current detector)
Current detector (CT) input (sample period)1 second
control methodTwo position control, PID control (with auto tuning function), PI control
Control operation cycle500 ms
Measurement temperature rangeK-200.0 to 200.0 掳 C, -100.0 to 400.0 掳 C, -100 to 1300 掳 C, -100 to 800 掳 F, -100 to 2400 掳 F
J-200.0 to 200.0 掳 C, -100.0 to 400.0 掳 C, -100.0 to 800.0 掳 C, -100 to 1200 掳 C, -100 to 1600 掳 F, -100 to 2100 掳 F
T-200.0 to 200.0 掳 C, -200.0 to 400.0 掳 C, 0.0 to 400.0 掳 C, -300.0 to 400.0 掳 F, -300.0 to 700.0 掳 F, 0.0 to 700.0 掳 F
S0 to 1700 掳 C, 0 to 3200 掳 F
R0 to 1700 掳 C, 0 to 3200 掳 F
E-200.0 to 200.0 掳 C, 0 to 1000 掳 C, 0 to 1800 掳 F
B0 to 1800 掳 C, 0 to 3000 掳 F
N0 to 1300 掳 C, 0 to 2300 掳 F
PLII0 to 1200 掳 C, 0 to 2300 掳 F
Wre5-260 to 2300 掳 C, 0 to 3000 掳 F
U-200.0 to 600.0 掳 C, -300.0 to 700.0 掳 F
L0.0 to 900.0 掳 C, 0 to 1600 掳 F
JPt100-50.0 to 150.0 掳 C, -200.0 to 500.0 掳 C, -300.0 to 300.0 掳 F, -300 to 900 掳 F
Pt100-50.0 to 150.0 掳 C, -200.0 to 600.0 掳 C, -300.0 to 300.0 掳 F, -300 to 1100 掳 F
Heater burnout detectionAlarm is detected by setting buffer memory (variable in the range of 0.0 to 100.0 A)
Operation mode0: Measured value monitor 1: Measured value monitor + temperature alarm 2: Measured value monitor + temperature alarm + control (selected by buffer memory)
Self-diagnosis functionBy adjustment data check, input value check, watchdog timer. Transistor output OFF when abnormality detected
memoryBuilt-in EEPROM (number of rewrites: 100,000 times)
Insulation method Insulation between analog input unit and sequencer by photo coupler Insulation between analog input unit and power supply by DC / DC converter Insulation between channels
I / O occupancy points8 points (can be counted either input or output)
Applicable sequencerFX2N, FX3U, FX2NC, FX3UC Connection to FX2NC requires FX2NC-CNV-IF. Connection to FX3UC requires FX2NC-CNV-IF or FX3UC-1PS-5V.
mass0.3 kg
Output specification
Output points2 points
Output methodNPN open collector transistor output
Rated load voltageDC5-24V
Maximum load voltageDC30V or less
Maximum load current100 mA
OFF leakage current0.1 mA or less
Maximum voltage drop when ONWhen 2.5V (max), 1.0V (TYP) 100mA is energized
Control output cycle30 seconds (variable from 1 to 100 seconds)
Power supply specification
Power supply5VDC 70mA ( internal power supply from sequencer) 24VDC + 10% -15% 55mA (external power supply)
Ambient temperature0 to 55 掳 C -25 to 75 掳 C
Relative humidity5 to 95% RH (without condensation)
Vibration resistanceWhen mounting DIN railFrequency: 10 to 57 HzSingle amplitude: 0.035 mm X, Y, Z each direction 10 times (total 80 minutes each)
Frequency: 57 to 150 HzAcceleration: 4.9 m / s 2 X, Y, Z each direction 10 times (total 80 minutes each)
Direct mountingFrequency: 10 to 57 HzSingle amplitude: 0.075 mm X, Y, Z each direction 10 times (total 80 minutes each)
Frequency: 57 to 150 HzAcceleration: 9.8 m / s 2 X, Y, Z each 10 times (total 80 minutes each)
Shock resistance147 m / s 2 , action time 11 ms, sine half-wave pulse 3 times in X, Y, Z directions
Noise resistantNoise voltage: 1,000 Vp-p, noise width: 1 渭s, rise time: 1 ns, period: 30 to 100 Hz noise simulator
Withstand voltageBetween analog input terminal and ground terminal: AC500V 1 minute
Insulation resistanceBetween analog input terminal and ground terminal: 5 M惟 or more with DC 500 V insulation resistance tester
groundType D Grounding (Grounding resistance: 100 惟 or less) < Do not connect to a common ground with a high-power system> Connect a dedicated ground or shared ground.
Use atmosphereCorrosive, no flammable gas, no severe conductive dust (dust)
Use altitudeIt can not be used in an environment pressurized to 2000 m or less at atmospheric pressure or higher. There is a possibility of breakdown.
Shipping Weight : 2 Kg